Chapter 6 Description of Function Codes
-155-
Function
code
Name
Description
(setting range)
Factory
Default
Change
F08.10
Accumulative running time 0h
~
65535h
—
**
F08.11
Product number
—
—
**
F08.12 is used to set the number of decimal places for load speed display. The following
gives an example to explain how to calculate the load speed:
Assume that F08.06 (Load speed display coefficient) is 2.000 and F08.12 is 2 (2 decimal
places). When the running frequency of the AC drive is 40.00 Hz, the load speed is
40.00x2.000=80.00 (display of 2 decimal places).
If the AC drive is in the stop state, the load speed is the speed corresponding to the set
frequency, namely, "set load speed". If the set frequency is 50.00 Hz, the load speed in the
stop state is 50.00 x 2.000 = 100.00 (display of 2 decimal places).
These function code can not be modify.
Heatsink temperature of inverter module is used to display the insulated gate bipolar transis-
tor (IGBT) temperature of the inverter module, and the IGBT overheat protection value of the
inverter module depends on themodel.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F08.12
Number of decimal places
for load speed display
0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
1
※
Function
code
Name
Description
(setting range)
Factory
Default
Change
F08.13
Accumulative power-on
time
0h
~
65535h
—
**
It is used to display the accumulative power-on time of the AC drive since the delivery. If the
time reaches the set power-on time (F09.16), the terminal with the digital output function 24
becomes ON.