96
Installation Manual
POWER
MIN INDUCTIVE,
PF
MIN,IND
MIN CAPACITIVE
PF
MIN,CAP
SETTLING
TIME
DESCRIPTION
5kW
70%
70%
3 Sec
Capacitive (Var production) and Induc-
tive] (Var absorption) minimum power
factor. Default PF = 1.0
PARAMETER
RATING
DESCRIPTION
S
rated
5 KVA
Apparent Power Rating (VA)
P
rated
3.5 KW
Output Power Rating (W)
V
nom
240V
Nominal AC EPS voltage (V)
V
min -
V
max
211 - 264V
AC EPS voltage range with function enabled (V)
VA
percent
5%
Reactive Power Accuracy
VA
ramp
500 VA/sec
Maximum ramp rate
Q
over-cap,max
3.57 VA
Maximum Rated Reactive Power Production (Capacitive,
Overexcited)
Q
under-ind,max
3.57 VA
Maximum Rated Reactive Power Absorption (Inductive,
Underexcited)
VA
slope,max
148 VA/V
Maximum slope of power over voltage
D
min -
D
max
235 - 240V
Deadband range (V)
Frequency Ride-Through
Power Factor
Volt-VAr Q(V)
FREQUENCY
ZONE
ZONE LIMITS (Hz) TRIP TIME
DESCRIPTION
HF2
F ≥ 62
0.166 sec
Trip time when the frequency is above 62Hz
HF1
60.5 < F < 62
58.5 ≤ F ≤ 60.5
300 sec
-
Trip time when the frequency range is between
60.5Hz and 62Hz
Not applicable when the frequency range is
between 58.5Hz and 60.5Hz
Nominal
LF1
57 ≤ F < 58.5
300 sec
Trip time when the frequency range is between
57Hz and 58Hz
LF2
F < 57
0.166 sec
Trip time when the frequency is below 57Hz
Grid Support Parameters
Содержание EverVolt EVAC-105-6
Страница 1: ...V 01012021 Installation Service Manual FOR AC AND DC COUPLED EVERVOLT SYSTEMS ...
Страница 65: ...65 Installation Manual Operation and Display Panel ...
Страница 76: ...76 Installation Manual Configuring the Hardware PV INPUT IS ONLY USED FOR EVERVOLT DC COUPLED SYSTEM ...
Страница 83: ...83 Installation Manual Step 5 Install the Generator wire ...