25
Installation Manual
Note, for the terminal block four bottom connections, check that
the minimum DC wire is stripped 23mm (0.9in). Wire lengths for the
four bottom connections can be check by removing set screw before
tightening and checking that the stripped wire completely protrudes past
the set screw hole. Secure to the screw to the torque value listed below.
Marathon Terminal Block Torque Specifications
Installing the Battery Enclosure & More
LINE
TORQUE
2/0 - 6 cual
8 cu
10 - 14 cu
120 lbf.in.
40 lbf.in.
35 lbf.in.
LOAD
TORQUE
4 - 6 cual
8 - 14 cu
35 lbf.in.
35 lbf.in.
Bottom Connections,
strip 23mm (0.9in)