41
Installation Manual
ASSEMBLY (CONTINUED)
6. BATTERY CONNECTION AND CHARGING
INFORMATION
Battery Connection & Charging Information
Note on DC Wiring and NEC
The maximum EverVolt DC charging current is 60 A for DC Coupled and
100A for AC Coupled systems.
Some electricians or installers may be unfamiliar with DC wiring in a
residential setting. Make note of all relevant codes, which may include:
1. NEC 690.31(G) for DC PV circuits in buildings.
2. NEC 215.12(C)(2) for correct DC wiring coloring.
3. NEC TABLE 310.15(B)(16) for Allowable Ampacities of Insulated
Conductors for Not More Than Three Current-Carrying Conductors in
Raceway (conduit wiring over 12").
4. NEC TABLE 310.15(B)(17) for Allowable Ampacities of Insulated
Conductors in Free Air (chassis wiring).
WARNING:
To reduce the risk of injury, use proper cable size
for battery's 150 A maximum current. It is very important for
system safety and efficient operation to use the appropriate
cable for battery connection.