29
Installation Manual
Wall Types
• Stud: The inverter will need to be mounted to the wall using Unistrut.
The Unistrut must be secured to two studs in the wall. There should
be two rows of Unistrut installed: one for the backplate and the other
for the side brackets.
• Solid: Use the backplate and mounting dimensions to mark for screw
locations.
Mounting the Inverter
CAUTION:
This inverter is heavy (74lb/33.6kg -- AC-Coupled,
88lb/40kg -- DC-Coupled). For safety, mounting should be
handled by two people.
ASSEMBLY (Continued)
2. MOUNTING THE INVERTER
Before installation, make sure nothing inside the package is damaged.
You should have received the following items in the package: hybrid
inverter, backplate, brackets, screws and this installation manual.
The following considerations must be taken into account before selecting
where to install:
• The unit cannot be mounted on flammable construction materials.
• The unit must be mounted to a solid surface.
• ALLOW 20CM (8IN) OF CLEARANCE TO THE SIDES AND 50CM (20IN)
TO THE TOP AND BOTTOM OF THE UNIT for proper air circulation to
dissipate heat.
• Before inverter placement, see battery operating temperature
requirements.
• The ambient temperature must be between 0°C and 50°C and
relative humidity must be between 5 and 85% to ensure optimal
operation. Do not operate where the temperature and humidity are
beyond the specified limits.
• The unit has a Pollution Degree rating of PD2. The unit must be
mounted in a protected area that is dry, free of excessive dust and
has adequate air flow.
• The unit was designed with an IP20 protection rating and is for indoor
applications only.
Содержание EverVolt EVAC-105-6
Страница 1: ...V 01012021 Installation Service Manual FOR AC AND DC COUPLED EVERVOLT SYSTEMS ...
Страница 65: ...65 Installation Manual Operation and Display Panel ...
Страница 76: ...76 Installation Manual Configuring the Hardware PV INPUT IS ONLY USED FOR EVERVOLT DC COUPLED SYSTEM ...
Страница 83: ...83 Installation Manual Step 5 Install the Generator wire ...