84
Installation Manual
Generator Control Mechanisms
Automatic Start Generator
The inverter can provide a start signal to control an automatic start
generator. The generator must be an electric-start model with two-wire
start capability. For other start-up methods, additional equipment may
be required. Those control signal can driver the generator when Grid
outages and battery is low level.
The 12V and Relay AUX terminals are used to start an automatic
generator.
• The 12V AUX terminals are a switched 12Vdc power supply and can
supply up to 0.25A.
• The Relay AUX terminals are “dry” contacts with no voltage and can
conduct up to 7A and up to 250Vac.
Function Signal Description
Power On
Grid
Available
Battery voltage < Battery cut-off discharge voltage
0 Vdc
Open
Battery voltage > Battery re-discharging voltage
0 Vdc
Open
Grid
Unavailable
Battery voltage < Battery cut-off discharge voltage
12 Vdc
Close
Battery voltage > Battery re-discharging voltage
0 Vdc
Open
Generator Application Schematic
On AC input II Terminal, there are 6 pin for control Generator. Control
port have defined as 1) Generator Power Line, 2) dry contact and 3)
12VDC source and. It could be used to remote control for external
generator.