78
Installation Manual
16. Generator Installation Instructions (Optional)
Introduction
The AC-Coupled / DC-Coupled Inverter can only work with “split-phase”
generators that delivers clean 120/240 VAC at 60Hz. Single-phase and
three-phase generators are not compatible with this inverter.
Note: Generator installations in North America are expected to bond the
neutral and ground at the main electrical panel.
Generator Sizing
• Available generator power may be limited by ratings for circuit breakers
and/or generator connectors. The maximum allowed AC circuit breaker
size is 40A.
• The generator should be sized to provide enough power and current
for all loads. The minimum recommended generator wattage is 6.25kW
because many generators may not be able to maintain AC voltage or
frequency for long periods of time if they are loaded more than 80% of
rated capacity.
Generator (Optional)