7 – 46
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
Installation of heating and refrigeration circuits for split systems
Condensate outlet of the hydro module
Drain hose version | Drain bend and drain hose version
Warning!
The drain hose must be in an environment which does not freeze .
Lay the drain hose so that closures or blockages cannot occur .
Do not insert the drain hose in a waste water system from which aggres-
sive gasses such as ammonia gas, sulphur gas etc . can escape .
➤
Push a standard hose with an internal diameter of 15 mm (to be pro-
vided by the customer) over the water drain . Ensure that the drain
hose is securely in place . If necessary, secure the hose with a hose
clamp (to be provided by the customer) .
➤
Route the drain hose with a constant downward slope into a suitable
collecting vessel for the condensate .
7.3 Condensate outlet of the hydro module
6.3.1 Drain hose version
1
1
Water drain
➤
Mount the enclosed drain bend with a seal on the underside of the
hydro module as shown in the figure .
➤
Push a standard hose with an internal diameter of 17 mm (to be
provided by the customer) over the drain bend . Ensure that the drain
hose is securely in place . If necessary, secure the hose with a hose
clamp (to be provided by the customer) .
➤
Route the drain hose with a constant downward slope into a suitable
collecting vessel for the condensate .
6.3.2 Drain bend and drain hose version
1
Drain bend
2
Seal
3
Water connection
1
2
3