7 – 43
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
7
Hydraulic &
refr
ig. circuits
Installation of heating and refrigeration circuits for split systems
Connecting the water pipes to the hydro module
➤
Insulate the two water connections using the enclosed PS moulded
parts and the long cable ties as shown in the figure .
➤
Insulate the pipes in accordance with the latest UK building regula-
tions, although the below is recommended:
1
PS foam
2
Water connection
3
Cable ties, long
Type of pipelines
Minimum thickness of insula-
tion layer
Internal diameter up to 22 mm
20 mm
Internal diameter from 22 mm to 35 mm
30 mm
Internal diameter from 35 mm to 100 mm
Same internal diameter
Warning!
Ensure that no impurities such as dirt or moisture can enter the pipe-
lines . Flush the pipelines before connecting the device, to remove
impurities . Impurities can damage the components of the device .