4 – 26
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
Location | Installing and fastening the devices
Location
Hydro module
• The hydro module is only suitable for indoor installation .
• The hydro module may not be installed in the vicinity of sources of
heat or steam . Laundry rooms or other very humid rooms are unsuit-
able, as the humidity can cause rust and damage the device .
• Good air circulation must be guaranteed .
• The room must have at least a minimum room volume of V
min
,
if no special machine room in accordance with BS EN 378 – Part 1
is available as a location .
V
min
= G
c
G = Refrigerant fill quantity in kg
c = Practical limit in kg / m³ (for R410A c = 0 .44 kg / m³
and for R407C c = 0 .31 kg / m³)
• The condensate from the condensate outlet of the hydro module
must drain away without trouble, as it can cause damage if not
drained correctly .
• The hydro module must be installed vertically on the wall .
The wall must be strong and solid to prevent vibrations .
• Mount the device close to the door .
• It must be installed at a height of at least 800 mm .
• Observe the minimum clearances (see figure) .
The following must also be observed:
• Consider the noise the circulation pump causes in the room .
• If the optional solar pump station cable is connected to the hydro
module and the solar pump station, the two devices should be
between two and eight metres apart . The solar pump station cable
must be at least 10 metres long . If not, system malfunctions can
result .
Warning!
The installation location must meet the following criteria:
4.1.3 Split systems: Hydro module
NOTE
Depending on the model, the hydro modules weigh between 43 and 52 kg .
1
1
2
1
1
Minimum clearance 300 mm
2
Minimum clearance 600 mm
Minimum clearances of the hydro
module to walls, ceiling and floor