4 – 22
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
Location | Installing and fastening the devices
Location
Monobloc systems or split system outdoor units
4 Location / Installing and fastening the devices
4.1 Location
4.1.1 Monobloc systems or splitsystem outdoor units
Weights of the monobloc units
Aquarea LT single-phase (one fan)
112 kg
Aquarea LT single-phase
153 kg
Aquarea LT three-phase
157 kg
Aquarea T-CAP single-phase
155 kg
Aquarea T-CAP three-phase
158 kg
Aquarea HT single-phase
155 kg
Aquarea HT three-phase
158 kg
Weights of the split system outdoor units
Outdoor unit 3 and 5 kW (one fan)
39 kg
Outdoor unit 7 and 9 kW (one fan)
66 kg
Outdoor unit* (two fans)
105 or 110 kg
*Depending on type
The installation location must meet the following criteria:
General
• Even and horizontal
• Load-bearing (see device weight table)
• No outside temperature under -20 °C (monobloc systems)
• Installation at a height sufficient to protect against weather influences
such as snow or water levels
• The height difference of the liquid system circuit may not exceed 7 m
(monobloc systems)
• Easy access for maintenance work
• Condensate must drain away easily
• No damage to other objects if water leaks
• If a solar installation is connected, the connection cable between
the solar pump station and the monobloc unit may not be longer than
10 metres