9 – 80
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
Commissioning
Programming
Temperature values
➤
Press the SELECT button to select the parameter .
➤
Use the UP or DOWN button to set the required temperature .
➤
Press the SET button to confirm the setting .
➤
Press the CANCEL button or wait 30 seconds to exit Setting mode .
Water
temperature
Outside
temperature
DEFROST
SETTING
STATUS
SERVICE
COOL
1. Low outside temperature
(-15 to +15 °C, Std . 0 °C)
COOL
DEFROST
SETTING
STATUS
SERVICE
2. High outside temperature
(-15 to +15 °C, Std . 15 °C)
DEFROST
SETTING
STATUS
SERVICE
COOL
3. Water supply target temperature
for heating mode at low outside tem-
perature (25 to 55 °C, Std . 55 °C)
DEFROST
SETTING
STATUS
SERVICE
COOL
4. Water supply target temperature
for heating mode at high outside
temperature (25 to 55 °C, Std . 32 °C)
DEFROST
SETTING
STATUS
SERVICE
COOL
5. Target temperature for switching
off heating mode (limit heating tem-
perature, 5 to 35 °C, Std . 24 °C)
DEFROST
SETTING
STATUS
SERVICE
COOL
6. Outside temperature for switching
on the additional electric heater
(-15 to +20 °C, Std . 0 °C)
DEFROST
SETTING
STATUS
SERVICE
7. Water supply target temperature in
cooling mode (5 to 20 °C, Std . +16 °C)
DEFROST
SETTING
STATUS
SERVICE
COOL
8. Target temperature of the hot-
water tank (40 to 75 °C, Std . +55 °C)
Note
No target temperatures
can be entered for the water
supply temperature in cooling
mode on the operator control
panel of the SDF versions .