7 – 49
Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
7
Hydraulic &
refr
ig. circuits
Installation of heating and refrigeration circuits for split systems
Condensate outlet of the outdoor unit
7.5 Condensate outlet of the outdoor unit
Warning!
If the outdoor unit is used in areas where the temperature can remain
below zero for 2 to 3 days, the drain bend or drain hose may not
be used, as the condensate could freeze and cause the device to
malfunction .
1
2
➤
Mount the enclosed drain bend with a seal on the underside of the
outdoor unit as shown in the figure .
➤
Push a standard hose with an internal diameter of 17 mm (to be pro-
vided by the customer) over the drain bend . Ensure that the drain
hose is securely in place . If necessary, secure the hose with a hose
clamp (to be provided by the customer) .
➤
Route the drain hose with a constant downward slope into a suitable
collecting vessel for the condensate .
1
Drain bend
2
Bottom plate
Note
When using the drain bend,
the outdoor unit should be
mounted on a substructure
at least 50 mm in height .