Recommended sequence of operations
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
5.4.4. Switch closing operation from isolating position
1.
Move the actuating shaft access handle in the grey
zone to its bottom position.
2. Closing operation:
a. Manual operation
(B driving mechanism). Insert
the lever in the switch access (grey area), move the
actuating arm to the end and turn clockwise 90º.
b. Motorised operation
(BM driving mechanisms).
Activate the corresponding operation command.
Figure 5.12.
Lever turn process
3.
Verify that the cubicle is in connected position.
Figure 5.13.
Switch
-
disconnector closed