IG-308-EN version 01; 03/06/2022
73
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Environmental information
9. Environmental information
[15]
This information is given on a label on the equipment itself.
cgm
.3 cubicles are defined as a pressure-sealed system,
according to IEC 62271-1, which contains hexafluoride
(SF
6
)
[15]
.
SF
6
is included in the Kyoto Protocol list of greenhouse
gases. SF
6
has a GWP (
Global Warming Potential
) of
22,200 units. (TAR, IPCC 2001).
At the end of the product's life, the SF
6
contained in it
must be recovered for processing and recycling, to prevent
it being released into the atmosphere. Extracting and
handling of SF
6
must be carried out by qualified personnel,
using a sealed piercing system.
For the usage and handling of the SF
6
, the indications listed
in IEC 62271-303 must be followed.
Management and treatment of the rest of materials must
be carried out in accordance with the country’s current
legislation.