IG-308-EN version 01; 03/06/2022
9
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
General description
1.4. Ratings table
Rated voltage [kV]
36
40.5
Frequency [Hz]
50
60
50
60
Rated current [A]
Busbars and cubicle interconnection
630
Feeder
630
Generator incoming
250
Rated short-time withstand current [kA]
With t
k
= (x) s
20* (1 s) | 25 (1 s)
20* (1 s) | 25 (1 s)
Peak value
50*/62.5
52*/65
50*/62.5
52*/65
Rated short-time withstand current of the generator incoming earthing circuit [kA]
With t
k
= (x) s
5 (1 s)
5 (1 s)
Peak value
12.5
13
12.5
13
Rated insulation level [kV]
Power frequency rated withstand voltage (1 min)
70/80
95/118
Lightning impulse rated withstand voltage
170/195
185/215
Internal arc classification according to IEC 62271-200
IAC AF/AFL
20*/25 kA (1 s)
20*/25 kA (1 s)
IAC AFLR
20*/25 kA (1 s)
20*/25 kA (1 s)
IP rating: gas tank
IP X8
IP rating: external enclosure
IP 2XD**
Standard unit colour [RAL]
grey 7035/blue 5005
Category of loss of service continuity [LSC]
LSC2
Compartmentalisation class
PM
* Tests carried out with current 21 kA/52.5 kA.
** Consult
Ormazabal
for other IP rating.
Table 1.6.
Characteristics
The values set out in this table are general for the
cgm
.3-huv system and are only valid when confirmed
by
Ormazabal
. Some cubicle models can withstand
partial values. For further information, please ask
Ormazabal
.