General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
General description
1.6. Operating conditions
Installation
Indoor
Maximum ambient temperature
+ 40 °C
Minimum ambient temperature
- 5 °C /- 30 °C
(b)
Maximum mean ambient temperature, measured over a 24-hour period
+ 35 °C
Maximum mean relative humidity, measured over a 24-hour period
< 95 %
Maximum mean relative humidity, measured over a 1-month period
< 90 %
Maximum mean vapour pressure, measured over a 24-hour period
2.2 kPa
Maximum mean vapour pressure, measured over a 1-month period
1.8 kPa
Maximum height above sea level
2000 m
Solar radiation
Negligible
Ambient air pollution (dust, smoke, corrosive and/or flammable gases, vapours or salt)
Insignificant
Vibrations caused by causes external to the switchgear or by seismic movements
Insignificant
(b)
Storage: - 40 °C.
Table 1.8.
Cubicle operating conditions
The specifications refer to the section
'Normal service
conditions for indoor cubicles'
in the IEC 62271-1
standard 'Common specifications for high-voltage
cubicles'.
For special service conditions: ambient temperature
above + 40ºC, installation between 2000 and 4000 m
above sea level, significant pollution level, or others
different to those described, check with
Ormazabal
.