IG-308-EN version 01; 03/06/2022
7
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
General description
1.3.3. Base
Made up of the cable compartment and the gas relief
compartment:
Cable compartment
This is located in the bottom front section of the cubicle
and has a cover interlocked with the earthing switch, thus
allowing front access to the medium-voltage cables.
As
standard
, it is designed to contain up to:
• Two shielded screw-in cable connectors (reduced) per
phase or one cable connector (reduced) plus surge
arrester (reduced) with space for the corresponding
incoming power cables.
• Cable ties for the power cables.
• Earthing bars.
As an
option
:
• Two symmetric cable connectors or symmetric cable
connector plus symmetric surge arrester.
Figure 1.3.
Cable compartment
Gas relief compartment
Ormazabal
's
cgm
.3-huv system is designed and
constructed to withstand at least the thermal and dynamic
effects of an arc of 25 kA for 1 second should a defect result
in an internal arc in the gas compartment. The system
conducts the gases generated in a fully controlled manner
to avoid any possible injury to people in the equipment
operation area.
Optionally
, a relief duct can be fitted in the rear of the
cubicle to redirect the gases to the top. Please check
with
Ormazabal
.
Содержание velatia cgm.3 system