IG-308-EN version 01; 03/06/2022
14
Storage
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
3. Storage
If it needs to be stored, the equipment must be placed on
dry ground or on top of damp-proof insulating material, still
in its original packing.
After prolonged storage, clean all the insulating parts
carefully before commissioning the equipment. The
enclosure should be cleaned with a clean, dry lint-free cloth.
Figure 3.1.
Storage conditions
Storage must always be INDOORS, with the following
conditions recommended:
1.
Ambient air temperature should not exceed 40 ºC
and its mean value, measured in a period of 24 hours,
should not exceed 35 ºC.
2.
The ambient air temperature must not drop below
- 5 °C. There are also cubicles with storage temperature
up to - 40 °C.
3.
The switchgear must be protected from direct solar
radiation.
4.
Altitude, both in transport and in storage, must not
exceed 2000 m.
5.
The environmental air must not have any significant
contamination from dust, smoke, corrosive and/or
inflammable gases, vapours or salt.
6.
The switchgear must be protected from the rain, and
the humidity conditions must be as follows:
a.
the average relative humidity value, measured over
a period of 24 hours, must not exceed 95 %.
b.
the average water vapour pressure value, measured
over a period of 24 hours, must not exceed 2.2 kPa.
c.
the average relative humidity value, measured over
a period of one month, must not exceed 90 %.
d.
the average water vapour pressure value, measured
over a period of one month, must not exceed
1.8 kPa.
7.
During transport, vibrations caused by external factors
or seismic movements must be insignificant.
Any other conditions must be notified beforehand,
since the equipment must be factory-adjusted to
atmospheric pressure at the destination.
If this is not the case, the pressure gauge needle may
indicate an incorrect value, even if the equipment's
internal pressure is correct.