Installation
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
4.6. Connecting the cubicles
The cubicles must be joined as indicated in
Ormazabal
's
RA-163
spares and accessories document,
which is supplied with the materials kit for connecting
cubicles.
4.7. Earthing the switchgear
When connecting the general earth collector, follow the
figure below.
Figure 4.11.
Equipment earthing
1.
Bolt the earthing flatbar between every two medium-
voltage cubicles, in the rear section, using two
hexagonal M8 x 20 bolts. Apply a torque of 15 Nm.
Tools:
13 mm open-end wrench
Torque wrench with 13 mm adapter.
2.
Connect the end earthing bar, marked with the symbol
, to the general earth connection of the facility.
Earthing the equipment is an essential condition for
safety.