General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Installation
4.3. Minimum installation distances
[5]
For any questions, please ask
Ormazabal
.
[6]
In each case, bear in mind which cable is to be used in the particular installation.
The minimum distances to the walls and roof which must
be maintained in the facility are as follows:
Figure 4.2.
Minimum installation distances
Minimum distances [mm]
Side wall (a)
100
Roof (b)
1050
Front clearance (c)
500*
Function
Rear wall (d)**
-l/-v/-rc/-ma/-lv/-rbv
100
* An operating clearance of 1000 mm is recommended.
** 800 in the case of AFLR
Table 4.1.
Minimum distances
The measurements indicated in the table have been
obtained in accordance with the dimensions of the
test room for the gas-filled modules, according to
Annex A of Standard IEC 62271-200.
The space required to extend the assembly with an
additional cubicle is 250 mm plus the width of the new
cubicle
[5]
.
4.4. Recommended cable connection trenches
Minimum recommended dimensions based on the trench
dimensions used in the tests in accordance with Standard
IEC 62271-200. These dimensions may vary in accordance
with the radius of curvature of the cables used
[6]
.