IG-308-EN version 01; 03/06/2022
19
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Installation
Circuit-breaker function with AV/RAV driving mechanism
Front and rear cable input or output (D1)
Side cable input or output (D2)
Figure 4.4.
Dimensions [mm] of the cable trench for
cgm
.3-huv-v
with
AV/RAV driving mechanism.
Trench necessary for the circuit-breaker with AV/RAV driving mechanism function
Cable details
Approximate
radius of
curvature*
[mm]
Minimum depth
Cable insulation
Cable type
Cable
section
[mm
2
]
Cable
diameter
[mm]
D1
[mm]
D2
[mm]
H
eigh
t
1400 mm***
Dry insulation
One-core 18/30 kV
< 150**
41
555
750
750
185
43
590
800
800
240
45.2
640
300
47.5
685
850
900
400
48
745
Three-core 18/30 kV
< 150
92.7
805
1200
1200
H
eigh
t
1745 mm
Dry insulation
One-core 18/30 kV
< 150**
41
555
400
400
185
43
590
400
500
240
45.2
640
300
47.5
685
500
600
400
48
745
Three-core 18/30 kV
< 150
92.7
805
850
850
* Check against the data of the manufacturer of the cable used.
** 150 mm
2
cable valid up to 21 kA.
*** Exclusively for -v cubicles.
Table 4.3.
Trench necessary for the circuit-breaker with AV/RAV driving mechanism function