IG-308-EN version 01; 03/06/2022
46
Recommended sequence of operations
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
4. Switch-disconnector opening operation:
a. Manual operation
(BM driving mechanism).
Insert the lever in the disconnector actuating shaft,
move the actuating arm to the end and turn anti-
clockwise 90º.
b. Motorised operation
(BM driving mechanism).
Activate the corresponding operation command.
Figure 5.30.
Lever turn detail
5.
Remove the lever. The handle returns to its original
position. Verify that the cubicle is in isolating position.
Figure 5.31.
Switch
-
disconnector open