IG-308-EN version 01; 03/06/2022
65
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Safety elements
6. Safety elements
6.1. Acoustic earthing prevention alarm
[14]
Incompatible with use of
ekor
.ivds
units
The
ekor
.sas acoustic alarm unit is associated to the
ekor
.vpis voltage presence indicating relay and to the earth
shaft actuator. The alarm is activated when there is voltage
in the functional unit's medium-voltage feeder and the
lever is inserted in the earthing switch shaft. A sound then
indicates that a short-circuit or zero voltage may occur in
the network if the operation is carried out.
Operation of the unit is assured within the same operating
range as the
ekor
.vpis unit associated with it
[14]
.
Audible alarm
ekor
.sas for line position.
Figure 6.1. ekor
.sas unit
6.2. Interlocks
The switchgear is provided with interlocks, which ensure
the following conditions:
1.
The switch-disconnector and the earthing switch
cannot both be in closed position at the same time.
2.
The cubicles have an interlock which prevents access
to the medium-voltage cable compartment whenever
the earthing switch is not closed. In normal operation,
this earthing switch cannot be opened if the cable
compartment cover is not in place.