48
Sun Datacenter InfiniBand Switch 648 Installation Guide • May 2010
3. Look for any light reflection inconsistencies.
A bent pin reflects light differently, either brighter or darker than the surrounding
pins.
Note –
Do not look at the individual pins, rather look at all of the connector’s pins
as a whole. A bent pin will be apparent.
4. Identify the connector with a pin that needs repair and note this.
5. Look for any contaminants that might be present.
These contaminants might appear as light dots near the pins.
6. Move your head down to the next connector and inspect its pins, repeating
through
7. Continue in this manner for all connectors in that column.
8. Repeat
to
for fabric card slot 1 to fabric card slot 8.
9. Identify the midplane line card connectors.
See
“Identify the Midplane Line Card Connectors” on page 48
Related Information
■
“Inspecting the Fabric Cards for Installation” on page 51
■
“Suggested Tools for Installation” on page 19
▼
Identify the Midplane Line Card Connectors
1. Identify the prerequisite and subsequent tasks you must perform in
conjunction with this procedure, to install the switch.
See the table in
“Installation Sequence” on page 20
.
2. Observe the front of the midplane.
The front side of the midplane has an 9x9 matrix of XBOW connectors that
interface with the line cards.
Содержание Sun Datacenter InfiniBand Switch 648
Страница 1: ...Sun Datacenter InfiniBand Switch 648 Installation Guide Part No 820 7738 12 May 2010 Revision A ...
Страница 8: ...viii Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 134: ...124 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 140: ...130 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...