Installing the Switch
85
3. Set the netmask for the CMC:
where
netmask
is the netmask. Typically, the netmask is
255.255.255.0
.
However, your network environment subnet might require a different netmask.
Use a netmask number most appropriate to your environment.
4. Set the IP address for the CMC gateway:
where
gateway_IP_address
is in the form of
xxx.xxx.xxx.xxx
.
5. Open a Telnet session and connect to the CMC by specifying the CMC’s
network address.
For example:
6. Login as
root
using the
root
password.
The
#
prompt is displayed.
Note –
As shipped, the
root
password is not set and therefore not required. Press
the Enter key when prompted for the password. Refer to the
Sun Datacenter
InfiniBand Switch 648 Administration Guide
for instructions on how to set the
root
password.
7. Verify the CMC status.
See
“Verify the CMC Status” on page 86
.
Related Information
■
Switch Command Reference
,
setlanconfig
command
#
clia setlanconfig 1 6
netmask
#
clia setlanconfig 1 12
gateway_IP_address
%
telnet 123.45.67.89
Trying 123.45.67.89...
Connected to 123.45.67.89.
Escape character is ’^]’.
shmm1500 login:
shmm1500 login:
root
Password:
password
#
Содержание Sun Datacenter InfiniBand Switch 648
Страница 1: ...Sun Datacenter InfiniBand Switch 648 Installation Guide Part No 820 7738 12 May 2010 Revision A ...
Страница 8: ...viii Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 134: ...124 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...
Страница 140: ...130 Sun Datacenter InfiniBand Switch 648 Installation Guide May 2010 ...