d. Slowly move the connector in.
As you slide the connector in, the top of the shell should scrape against the
underside of the top of the CXP receptacle.
■
If the cable stops or binds after about 5 mm (1/4 in.) travel, back out and
repeat from
■
If the connector stops or binds with about 2 mm (1/8 in.) still to go, back out
and repeat
.
e. Continue to push the connector in until the hooks catch onto the top of the
receptacle.
5. Curve the cable to the right through the branches of the cable tree.