Sun Datacenter InfiniBand Switch 648 Installation Guide • May 2010
3. Check for fabric card power faults:
If an installed fabric card is shown to
FAIL
, investigate why.
4. Check fabric card internal voltages:
If an installed fabric card is shown to
FAIL
, investigate why.
5. Verify that the fans are operating:
If a fan’s speed is too low or the fan has
STOPPED
, investigate why.
6. Verify that the switch chips in the fabric cards are operational:
If an installed fabric card is shown as
not boot correct
, investigate why.
Note –
Fabric card fillers do not have any switch chips. The
checkswitches
command does not display any information about fabric card fillers.
7. Retrieve each fabric card’s firmware versions:
where
slot
is the slot number for the installed fabric cards. For example:
8. Repeat
and record the information for each fabric card and compare to
identify any discrepancies.
All fabric cards should have the same firmware versions.
#
checkpwrfault | grep FC
#
checkvoltages
#
checkfans
#
checkswitches | grep FC
#
getfwversion fc
slot
#
getfwversion fc 0
FW versions for FC 0
H8 version : 0.1.1
FC FPGA version : 1.0.1
I4 FW image version : 7.2.00
#