InfiniBand Cable Cautions
To prevent InfiniBand cable damage, you
must
follow these cautions:
Do not uncoil the cable, as a kink
might occur. Hold the coil closed
as you unroll the cable, pausing
to allow the cable to relax as it is
unrolled.
Do not step on the cable or
connectors. Plan cable paths away
from foot traffic or rolling loads.
Do not pull the cable out of the
shipping box, through any
opening, or around any corners.
Unroll the cable as you lay it
down and move it through turns.
Do not bend the cables to a radius
tighter than 85 mm (3.4 inches).
Ensure that cable turns are as
wide as possible.
Do not twist the cable to open a
kink. If it is not severe, open the
kink by unlooping the cable.
Do not pack the cable to fit a tight
space. Use an alternative cable
route.