WIRING EXAMPLES

INSTALLATION INSTRUCTIONS

      senvainc.com   1-866-660-8864    (F)1-503-296-2529    9290 SW Nimbus Ave.    Beaverton Oregon 97008

C-2330, 

Auto-Calibrating

Mini Split-Core Digital 

Output

Failure to follow these instructions will result in 

death or serious injury.

•    Follow ALL requirements in NFPA 70E for safe work practices 

and for Personal Protective Equipment (USA) and other appli-

cable local codes when installing this product

•    Only qualified electrical personnel should install this product.  
•    Read, understand, and follow all instructions thoroughly
•   Install only on insulated conductors
•    Lock out and tag out all power sources prior to installation.  

Use properly rated voltage sensing instrument to determine 

no voltage is present   

Failure to follow these instructions could result in 

death or serious injury.

•   Equipment monitored/operated by this device may start 

without warning.  Keep clear of apparatus at all times

IMPORTANT  WARNINGS

•   Only qualified  trade installers should install this product
•   This product is not intended for life-safety applications
•   Do not install in hazardous or classified locations
•   The installer is responsible for all applicable codes
•    This product must be installed in a suitable electrical enclosure

Automated equipment may 
start without warning

DANGER

WARNING

!

Hazard of electrical shock, explosion, 
and arc flash

DANGER

WARNING

!

PRODUCT APPLICATION LIMITATION:

Senva products are not designed for life or safety applications. Senva products 

are not intended for use in critical applications such as nuclear facilities, human 

implantable device or life support. Senva is not liable, in whole or in part, for 

any claims or damages arising from such uses.

CALIBRATION

1.  No calibration is necessary for normal applications. Sensor 

will automatically learn motor run current and adjust threshold 

as needed.

2.  To manually re-calibrate sensor, press and hold button for 1 

second. LED will blink twice. Sensor will discontinue automati-

cally threshold adjustment.

3.  To set sensor to go/no mode, press and hold button for 5 

seconds. LED will blink 3 times.

INSTALLATION

1.  Determine mounting location for the sensor near the 

conductor to be monitored. The sensor should be located AT 

LEAST 1/2” from any uninsulated conductor.

2.  Sensor features a flexible iris which allows the sensor to 

hang on the conductor if local codes permit. A bracket is 

included for screw mounting or attaching to DIN rail. For screw 

mounting, drill two 3/32” pilot holes using the bracket as a 

template; ensure no drill shavings are present in enclosure. At-

tach bracket with screws provided.

3.  Clamp sensor around INSULATED CONDUCTOR ONLY, 

600VAC MAX to be monitored.

4.  Snap the sensor into the mounting bracket.
5.  Wire the output of the sensor to a control panel digital 

input loop not to exceed 30VAC/DC wetting voltage. Tighten 

terminals to 3.5 in-lb.

Disconnect, lock out and tag out all 
power supplies during installation

V+

DI

CONTROLLER

(SINKING)

(SOURCING)

(AC)

INSULATED PRIMARY

AC CONDUCTOR

600VAC MAX

V+

DI

24VAC

DI

V+

DI

ALTERNATE

CONTROLLER ARRANGEMENTS

DI

DI

VAC

GND

NOTE: Device is NOT polarity sensitive.

v

Status Output

0.5A @ 30VAC/DC

Normally Open

Fast learn mode:

Press/hold 1 sec

LED 2 fast blinks

Go/No mode:

Press/hold 5 sec

LED 3 fast blinks

Slow blink

Normal

Fast blink

Alarm

Optional Manual Setup:

3PZS

Not for use on variable speed drives.

Use C-2350-VFD for VFD applications.