© 2006-2007 Server Technology, Inc. All rights reserved.
Rack-Mount Fail-Safe Transfer Switch
Installation and Operations Manual
•
C-8HFx
C-16HFx
Страница 1: ... 2006 2007 Server Technology Inc All rights reserved Rack Mount Fail Safe Transfer Switch Installation and Operations Manual C 8HFx C 16HFx ...
Страница 2: ...hesia ventilators infusion pumps and any other devices designated as critical by the U S FDA Notices 301 0128 1 Rev B 081007 Copyright 2006 2007 Server Technology Inc All rights reserved 1040 Sandhill Drive Reno Nevada 89521 USA All Rights Reserved This publication is protected by copyright and all rights are reserved No part of it may be reproduced or transmitted by any means or in any form witho...
Страница 3: ...ditional Required Items 6 Safety Precautions 6 Installing the Power Input Retention Bracket 7 Mounting 7 Optimizing the Transfer Thresholds 7 Connecting to the Power Source 7 Connecting Devices 7 CHAPTER 3 OPERATIONS 8 Modes of Operation 8 CHAPTER 4 APPENDICES 9 Appendix A Technical Specifications 9 Appendix B Warranty Product Registration and Support 11 ...
Страница 4: ... 7 4 Connect the devices to the Fail Safe Transfer Switch 7 Technical Support Experience Server Technology s FREE SMARTER Technical Support Learn more Server Technology understands that there are often questions when installing and or using a new product Free Technical Support is provided from 6 00 AM to 7 00 PM Monday Friday Pacific Time Server Technology Inc 1040 Sandhill Drive Tel 775 284 2000 ...
Страница 5: ... configures the brownout over voltage switching points 2 The power inlets connect the Rack Mount Fail Safe Transfer Switch to the electrical power sources 3 LEDs display the input feeds power status 1 2 3 Figure 1 Sentry Rack Mount Fail Safe Transfer Switch Views Rack Mount Fail safe Transfer Switch Introduction 5 Installation and Operations Manual ...
Страница 6: ...ialisé doit avoir un disjoncteur ou une protection de fusible CDUs ont été conçus sans disjoncteur général ni fusible pour éviter que cela devient un seul endroit de panne C est la responsabilité du client de fournir une protection adéquate pour le circuit alimentation spécialisé Protection de capacité équivalant à la puissance de l équipement et respectant tous les codes et normes applicables Les...
Страница 7: ...sed to optimize the transfer threshold by configuring the Transfer Switch for the nominal operational voltage of the installation The Transfer Switch uses this setting to calculate the brownout and over voltage threshold 13 To optimize the transfer threshold Select the voltage setting that most closely matches the nominal operating voltage of the power sources Connecting to the Power Source To att...
Страница 8: ...e blank and the remaining display will report the total current load for the unit Nominal Voltage Brownout Recovery Voltage Over Voltage 100V 87 0V 93 0V 107 0V 113 0V 110V 95 7V 102 3V 117 7V 124 3V 115V 100 0V 106 9V 123 0V 129 9V 120V 104 4V 111 6V 128 4V 135 6V 208V 181 0V 193 4V 222 6V 235 0V 220V 191 4V 204 6V 235 4V 248 6V 230V 200 1V 213 9V 246 1V 259 9V 240V 208 8V 223 2V 256 8V 271 2V No...
Страница 9: ... 40 C 40 to 185 F 40 to 85 C Elevation above MSL 0 to 10 000 ft 0 to 3000m 0 to 50 000 ft 0 to 15000m Relative Humidity 10 to 90 non condensing 10 to 90 non condensing Dimensions H x W x D Weight C xHF 3 5 x 17 0 x 14 0 in 90 x 437 x 356 mm 20 7 lbs 9 4 kg Transfer Rate Power transfer 18 milliseconds Model Voltage Current Voltage Outlet Branch Circuit Phase Total Modele Tension Courrant Tension Pr...
Страница 10: ...du Règlement sur le matériel brouilleur du Canada European Union Notification Products with the CE Marking comply with both the EMC Directive 89 336 EEC and the Low Voltage Directive 73 23 EEC issued by the Commission of the European Community Compliance with these directives implies conformity to the following European Norms EN55022 Electromagnetic Interference EN55024 Electromagnetic Immunity EN...
Страница 11: ...Technical Support Learn more Server Technology understands that there are often questions when installing and or using a new product Free Technical Support is provided from 6 00 AM to 7 00 PM Monday Friday Pacific Time Server Technology Inc 1040 Sandhill Drive Tel 775 284 2000 Web www servertech com Reno Nevada 89521 USA Fax 775 284 2065 Email support servertech com Return Merchandise Authorizatio...
Страница 12: ...ive Sienna Court Singapore Reno NV 89521 The Broadway 65 0 6829 7008 Tel United States Maidenhead 65 0 6234 4574 Fax 1 775 284 2000 Tel Berkshire salesint servertech com 1 775 284 2065 Fax SL6 1NJ sales servertech com United Kingdom www servertech com 44 0 1628 509503 Tel www servertechblog com 44 0 1628 509100 Fax salesint servertech com ...