background image

B-1909-1(0)

INSTRUCTION SHEET - HS1C Series 

Solenoid Type Safety Switch

2016.08

2

Specifications and Ratings

*2 Basic insulation of 4kV impulse withstand voltage is ensured between different 

contact circuits and between contact circuits and LED or solenoid in the enclosure. 

When both SELV (safety extra low voltage) or PELV (protective extra low voltage) 

circuits and other circuits (such as 230V AC circuits) are used for the solenoid 

power and contact circuits at the same time, the SELV or PELV requirements are 

not met any more.

*3 The actuator locking strength is rated at 1,500N of static load. Do not apply a load 

higher than the rated value. When a higher load is expected to work on the 

actuator, provide an additional system consisting of another safety switch without 

lock (such as the HS5D safety switch) or a sensor to detect door opening and stop 

the machine.

*4 F1max. is maximum force. The actuator’s guard-locking force Fzh is calculated in 

accodance with GS-ET-19 :

Ratings approved by safety agencies

1

Type

*1  Type Nos. in [  ] are not supplied as 

standard.

 

Contact IDEC if required.

Main Circuit : 10A, Auxiliary Circuit : 3A

IEC60204-1/ EN60204-1

CSA C22.2 No.14, GB14048 5

GS-ET-19, UL508

IEC60947-5-1, EN60947-5-1

EN ISO / ISO14119

IP67 (IEC60529)

100 mΩ maximum (Ini ial value)

20 N minimum

11 mm minimum

0.05 to 1.0 m/s

900 operations/hour

Actuator Tensile Strength

when Locked

Operating Speed

Operating Frequency

‹Ue , Ie›

(Reference Values)

Contact Ra ings

Thermal Current ‹Ith›

Applicable Directives

Applicable Standards

AC 

DC 

AC 

DC

Standards for Use

Degree of Protection

Contact Resistance

Direct Opening Force

Direct Opening Travel

Main 

Circuit

Auxiliary 

Circuit

Induc ive load

 

(DC-13) 

      

Resistive load

 

(DC-12)

Induc ive load

 

(AC-15) 

Resistive load

 

(AC-12)

Induc ive load

 

(DC-13) 

Resistive load

 

(DC-12)

Induc ive load

 

(AC-15) 

Resistive load

 

(AC-12)

  

 

   

 

30V  125V   250V
10A      10A        6A
10A       5A         3A
 6A          -            -
 3A       0.9A         -
   -          3A        3A
   -           -          3A
 3A          -            -
 3A       0.9A         -

        

  

Low Voltage Direc ive, Machinery Directive

Operating Condition

Operating Temperature

Operating Humidity

Pollution Degree

Al itude

-25 to +50°C (no freezing)

45 to 85%RH (no condensation)

3

2,000m maximum

300V (Between ground and LED, solenoid circuit : 60V)

4kV (Between ground and  LED, solenoid circuit : 2.5kV)

Raed Insulation voltage ‹Ui›

Inpulse withstand voltage ‹Uimp›

Class of Protection

Class 

I

 ( EC61140) *2

B10d

2,000,000 (EN ISO 13849-1 Annex C Table C.1)

Shock Resistance
Vibration Resistance

Operating Extremes :10 to 55Hz, half amplitude 0.5mm 

Damage Limits : 30Hz, half amplitude 1.5mm
Fzh=1,500N minimum   

F1max.=1,950N minimum (GS-ET-19)  *3, *4

Damage Limits : 1,000m/s

2

Mechanical Durability

1,000,000 operations min. (GS-ET-19)

Electrical Durability

(900 operations / hour)

1,000,000 operations min. (AC/DC 24V 100mA)

100,000 opera ions min. (AC-12 250V•6A)

 

 

 

(Examples of Mounting on Hinged Doors)

(Examples of Mounting on Sliding Doors)

3

Mounting Examples

• Install the interlock switch on the immovable machine or guard, and install the 

actuator on the movable door.  Do not install both interlock switch and actuator on 

the

 

movable door, otherwise  he angle of insertion of the actuator to  he safety switch 

may become inappropriate, and failure will occur.

Hinged

Door

HS9Z-A2

Actuator

Safety 

Switch

Door

Safety 

Switch

HS9Z-A1

Actuator

Lock

Door Stop

Latch

HS9Z-A1

Actuator

When the center of the hinged door is on 

the  extension line of the contact surface 

of actuator and safety switch.

When  he center of the hinged door is on 

the extension line of  he actuator 

mounting surfase.

When using the safety switch for a hinged door, the minimum radius of the applicable 

door is shown in the following figures.

Minimum Radius of Hinged Door

Door Hinge

Minimum Radius

230mm

Door Hinge

Minimum Radius

130mm

Minimum Radius

400mm

Minimum Radius

240mm

Door Hinge

Door Hinge

R(Red), G(Green) (Φ12Lens)

LED lamp

10mA

24VDC

Approx. 10W

Rated Voltage × 10% minimum (at 20°C)

Rated Voltage × 85% maximum (at 20°C)

415mA

24VDC

250V AC,10A fast acting type fuse

 

 

 

 

 

Short-Circuit Protective Device

g

   

Cont ct Resistance

Conditional short circuit current 100A(250V)

Illumination Color

Light Source

Rated Current

Rated Operating Voltage

Rated Power Consumption

Turn OFF Voltage

Turn ON Voltage

Rated Current

Rated Operating Voltage

Solenoid

Indicator

CAUTION

The figures shown above are based on the condition that the actuator enters and 

exits the actuator entry slot smoothry when the door is closed or opened. Since 

there may be deviation or dislocation of the hinged door, make sure of correct 

operation in the actual application before installation. 

Door Hinge

Minimum

Radius

50mm

Door Hinge

Minimum

Radius

80mm

• L-shaped actuator : HS9Z-A2

• Adjustable actuator : HS9Z-A3

Thank you for purchasing this IDEC product. Confirm that the delivered product is 

what you have ordered. Read this instruction sheet to make sure of correct operation.

In this operation instruction sheet, safety precautions are categorized in order of 

importance to Warning and Caution :

Warning notices are used to emphasize that improper operation may cause severe 

personal injury or death.

Caution notices are used where inattention might cause personal injury or damage to 

equipment.

INSTRUCTION SHEET

Original Instructions

Solenoid Type Safety Switch

HS1C Series

S A F E T Y   P R E C A U T I O N S

CAUTION

WARNING

Fzh   =

maximum force (F1max.)

Safety coefficient (=1.3)

Circuit  Diagram No.

 

 Main Circuit  Auxiliary Circuit

 blank : 1NC+1NC 1NO/1NO

 1 : 1NC+1NC 1NO

 2 : 1NC+1NC 1NC+1NC

 3 : 1NC

1NC 1NC

Solenoid voltage

 

4 : DC24V

LED voltage

 

4 : DC24V

  [ 0 ] : Without LED

Solenoid unit mounting position

 

R : Right side

  [ L ] : Left side

Housing Color

 

R : Red 

Indicator Color

  G : Green

  R : Red

HS1C-R144R-R

(1) TÜV rating

 

AC-15 250V, 3A

(3) CCC rating

 

AC-15 250V, 3A

 

DC-13 125V, 0.9A

(2) UL, c-UL rating

 

3A, 250V ac, General Use

 

3A, 30V dc, Resistive

Отзывы: