EX Series Operating Manual
4-3. Remote Programming Control
By using External input voltage, you can program the output voltage and current.
The following is a description about analog programming.
Remote Voltage Programming
By using 0~5VDC input, you can program the output voltage from 0V to 100% voltage.
The following is a pin connection drawing.
< Figure. 4-3 Remote Voltage Programming >
Remote Voltage Programming setting
The factory default is set as local mode. If device is equipped with option, you should change
the setting and you can use remote voltage programming.
Before setting, you must complete external wiring.
If you do external wiring under the remote cotrolling, the DUT can be damaged because of power
supply's output voltage floating
Warning
supply s output voltage floating.
▌Turn on the power supply
After turned on, check the power supply displays"
**OUTPUT OFF**
" Mode.
▌Press the limit display key and hold 3 seconds.
LCD Display
1. V PROG
LCD Display
▌In other to use remote voltage programming, press the limit display key.
LCD Display
local
▌Press the cursor keys to change to remote mode
LCD Display
REMOTE
LCD Display
REMOTE
▌In other to apply and store the mode changes, press the limit display key.
LCD Display
SAVED
▌When you turn on the power next time, start with your current settings.
- 56 -
Содержание EX Series
Страница 2: ......
Страница 104: ...EX Series Operating Manual 104...
Страница 105: ...EX Series Operating Manual 105...
Страница 107: ...EX Series Operating Manual 2U 2 6KW 5KW Product Outside Dimension 2U 2 6KW 5KW Product Rear Feature 107...
Страница 108: ...EX Series Operating Manual 4U 5 1KW 10KW Product Outside Dimension 4U 5 1KW 10KW Product Rear Feature 108...
Страница 113: ...EX Series Operating Manual Reliability Durability Life time Test System Solution 113...