6-8. OCP USE
▌Enable or disable the "Over Current Protection" function.
▌In case of a like inductivity DUT, motor, big capacity DUT and etc, occurs "OCP trip" frequently
so if it is not convenient to use the power supply, you can set disable of "OCP USE" mode.
▌If disable the "OCP USE", the power supply doesn't cut the DC source when current level is
over OCP setting level.
▌F
ti
▌Function
> DISABLE
Disable "OCP USE" mode.
> ENABLE
nable "OCP USE" mode.
OCP USE
▌Power switch on in a pressing "FACTORY" key.
▌Power switch ON
▌When appearing "1. user-mem clear" message, release "FACTORY" key.
In a pressing
▌Enter to "6. OCP USE" mode by using cursor key.
▌In other to set, press the "FACTORY" key one more time.
LCD Display
Release
enable
▌Set the "enable" mode by using cursor key.
LCD Display
▌To finish the "OCP USE" mode, press the "FACTORY" key one more time.
LCD Display
disable
done
≫ Related remote interface command
FACT:OCP {DIS|ENA}
FACT:OCP?
Return Value(1, 0)
Apply:
FACT:OCP?
Return value : 0
"OCP USE" mode is disable state
FACT:OCP ENA
"OCP USE" mode changed to
enable state
- 80 -
Содержание EX Series
Страница 2: ......
Страница 104: ...EX Series Operating Manual 104...
Страница 105: ...EX Series Operating Manual 105...
Страница 107: ...EX Series Operating Manual 2U 2 6KW 5KW Product Outside Dimension 2U 2 6KW 5KW Product Rear Feature 107...
Страница 108: ...EX Series Operating Manual 4U 5 1KW 10KW Product Outside Dimension 4U 5 1KW 10KW Product Rear Feature 108...
Страница 113: ...EX Series Operating Manual Reliability Durability Life time Test System Solution 113...