— 6-7 —
6.4.2. Ground Connection and Wiring
l
For grounding Driver Unit, use heavy gage cable as possible, such as a flat braided copper cable
or a wire 3.5mm
2
(AWG 10) or larger.
!
Caution : • All the ground lines must be connected at one point and the grounding
resistance must be under or equal to 100
ス
.
• Connect the shield of the signal shielded cable (CN2) to the FG
terminals (or SG terminals) of the user’s controller. If runaways are
caused by noise, connect the shield to the FG terminal of the Driver
Unit.
• Earth the rack base by bolts when the Motor is electrically isolated
from the other machines.
l
Figure 6-3 shows the wiring example. (This is provided as an example, not the instruction.)
Figure 6-3: Wiring Example
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание MEGATHRUST ESA-LYB2T15-21
Страница 7: ...Blank Page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 23: ...3 4 Blank page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 35: ...4 12 Blank Page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 73: ...6 12 Blank Page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 155: ...11 10 Blank Page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 187: ...12 32 Blank Page Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 225: ...A 10 Figure A 10 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 228: ...A 13 Figure A 16 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...