7. Operational Function
— 7-6 —
7.1.5. Program Start: RUN
Internal Program Channel Selection: Input PRG0 to PRG7
This input starts to execute a program.
Table 7-8: Signal logic of the input RUN
Logic
Description
↓
(ON
→
OFF)
Invalid
↑
(OFF
→
ON)
Start program
The input RUN starts execution of the program in the internal program channel specified by the inputs
PRG0 to PRG7.
The channel number is specified by the binary number represented by ON and OFF of the inputs
PRG0 to PRG7.
Please confirm all of the following conditions are met before execution of the program.
Otherwise, the warning F5 (Program error) occurs.
1) The System is not in the middle of execution of a program.
Check if the output BUSY (In-operation) is open.
2) The channels specified by the outputs PRG0 to PRG7 have the proper settings of commands and
parameters.
3) The conditions to execute the programs in the channels are in place. For example, the Motor
servo must be activated if a positioning command is programmed.
4) There is no alarm or warning is occurred. The input STP (Motor stop) is OFF.
Refer to “6.3.2. Program Positioning Operation” for the procedures of program positioning operation.
Содержание EDD Megatorque Motor
Страница 8: ... Blank Page ...
Страница 92: ...4 RS 232C Communication and USB Communication 4 16 Input the command WWC for cancellation of Multi monitor ...
Страница 146: ...6 Operation 6 38 Blank Page ...
Страница 184: ...7 Operational Function 7 38 Blank Page ...
Страница 211: ...8 More Advanced Function 8 27 ...
Страница 246: ...8 More Advanced Function 8 62 Blank Page ...
Страница 332: ...9 Details of Command and Parameter 9 86 Blank Page ...
Страница 340: ...10 Maintenance 10 8 Blank Page ...
Страница 364: ...11 Alarm and Warning 11 24 Blank Page ...