11. Alarm and Warning
— 11-5 —
11.2. List of Alarm and warning
11.2.1. Normal State
The table below shows the condition of the System when the input SVON (Servo on) is activated and the
System is ready for the operation command, the System.
For the execution of operation, clear the input STP (Stop).
Table 11-3: The condition for command acceptance
POWER
LED
7-seg.
LED
Output
DRDY
Output
WRN
Output
OTPA
and
OTMA
Output
SVST
Motor condition
Green
Close
Closed
Closed
Closed
Servo-on
!
Caution : The outputs DRDY (Driver ready), WRN (Warning) and OTPA/OTPM
(Travel limit) are normally closed and they open for reporting abnormality.
The shipping set of the outputs WRM and OTPA/OTMA is negative logic.
If the Motor does not move even no alarm or warning is reported, the System may be in the condition
shown in “Table 11-4: condition when the Motor does not move even in normal state.”
In the condition shown in the table below, the Motor gets in the servo-off state and the dynamic
brake is functioning to brake the Motor.
When the initialization of the CPU takes longer than 10 seconds at the power-on, the control
circuit is not functioning normally. Refer to “11.3.1. CPU Error” for the cause and remedy.
Table 11-4: condition when the Motor does not move even in normal state
POWER
LED
7-seg.
LED
Output
DRDY
Output
WRN
Output
OTPA
and
OTMA
Output
SVST
Motor
condition
System
condition
Cause
Remedy
Off
Off
Open
Open
Open
Open
Servo-off
The power is
not turned on.
The power is not
turned on.
Turn on the
power
Orange
Off
Open
Open
Open
Open
Servo-off
Initializing
CPU
The power is on, but
the CPU is being
initialized.
Wait for about 3
seconds
Green
Closed
Closed
Closed
Open
Servo-off
Servo-off
The input SVON is
not activated.
Activate the
input SVON.
The input SVON
is on, but the servo
is not on yet.
Wait until the
output SVST
closes.
Содержание EDD Megatorque Motor
Страница 8: ... Blank Page ...
Страница 92: ...4 RS 232C Communication and USB Communication 4 16 Input the command WWC for cancellation of Multi monitor ...
Страница 146: ...6 Operation 6 38 Blank Page ...
Страница 184: ...7 Operational Function 7 38 Blank Page ...
Страница 211: ...8 More Advanced Function 8 27 ...
Страница 246: ...8 More Advanced Function 8 62 Blank Page ...
Страница 332: ...9 Details of Command and Parameter 9 86 Blank Page ...
Страница 340: ...10 Maintenance 10 8 Blank Page ...
Страница 364: ...11 Alarm and Warning 11 24 Blank Page ...