8. More Advanced Function
— 8-29 —
8.5.3. Position Loop Dead Band
The parameter DBP is used to specify a dead band for the deviation of position loop. The deviation will be
zeroed when it is under the set data of the parameter DBP.
The dead band eliminates problems of positioning instability right after completion of positioning.
Table 8-30: Position loop dead band: DBP
Parameter
Function
Initial
setting
Data range
Unit
DBP
Sets a dead band to the position loop.
0
0 to 4 095
0.5 [pulse]
: Require an entry of the password.
The parameter DBP specifies a dead band on the position loop deviation in both sides of 0 (zero) and
zeroes the deviation that is under the DBP setting.
In some use conditions, slight vibration may occur due minute deviation. Provision of the dead band
eliminates such slight vibration.
If a dead band is specified, the repeatability of positioning accuracy will be deteriorated by the
amount of the dead band though the slight vibration may be eliminated.
The unit of the dead band is a half of pulse count.
(Corresponds to a half of the resolution of position sensor. Refer to “2.7. Driver Unit Specifications” for
the resolution of position sensor.)
Содержание EDD Megatorque Motor
Страница 8: ... Blank Page ...
Страница 92: ...4 RS 232C Communication and USB Communication 4 16 Input the command WWC for cancellation of Multi monitor ...
Страница 146: ...6 Operation 6 38 Blank Page ...
Страница 184: ...7 Operational Function 7 38 Blank Page ...
Страница 211: ...8 More Advanced Function 8 27 ...
Страница 246: ...8 More Advanced Function 8 62 Blank Page ...
Страница 332: ...9 Details of Command and Parameter 9 86 Blank Page ...
Страница 340: ...10 Maintenance 10 8 Blank Page ...
Страница 364: ...11 Alarm and Warning 11 24 Blank Page ...