No. Name
Description
Range
Min.
Max.
43
INDEX
* INDEX MODE
If this value is set in "0", mm unit is available.
If this value is set in "1", inch unit is available.
If this value is set in "2", index mode is available.
Index mode changes it's coordinate system from mm(inch) to degree.
In case of index system, the formula of machine scale is as follows.
SETUP-09 "SCALE" = Pulses per 1 revolution (360 deg) / 100
In general case, only setup-09 "SCALE" determines the machine scale
and setup-10 "DSCAL" is set in "1".
Don't make a fractional case that degrades the precision of machine,
as soon as possible. If machine scale is a fraction that has a decimal
point, user can raise up precision by the setup-10 "DSCAL".
The standard "TANGO-B" series has the 10000 or 20000 pulses per
1 revolution (the motor encoder pulse is internally multiplied by 4).
[Example 1] Case of fixed number
Motor encoder
: 2500 ppr
Pulse/revolution
: 2500 X 4 = 10000 ppr
Gear reduction
: 1 / 4
(Pulse/revolution)/100
: (10000 * 4) / 100 = 400
Setup-09 "SCALE" = 400
Setup-10 "DSCAL" = 1
[Example 2] Case of fraction number
(Don't make this case as possible as)
Motor encoder
: 2500 ppr
Pulse/revolution
: 2500 X 4 = 10000 ppr
Gear reduction
: 3 /1
(Pulse/revolution)/100
:10000/(3*100)=33.333=33333/1000
Setup-09 "SCALE" = 33333
Setup-10 "DSCAL" = 1000
0
2
44 SERVO
* AUTO SERVO ON
If this value is set in "1", the "auto servo on" function is available.
The "auto servo on" function makes the servo amplifier to operate
normally without external servo-on input. It is valid for all control mode.
When it is impossible to make servo-on state by external input (without
loader and Setup-23 "I3/SM" = 0 or 2), this function supplies the servo
amplifier with automatic servo-on function before operation.
0
1
45
DISPL
* LCD DISPLAY
Determine the display mode of LCD installed on loader as follows.
It can be changed anytime regardless of servo on state.
0
Current position, selected file no. executed program line
1
Work counter, general purpose counter 0
2
All contents of Setup-36 "SEGDP"
0
2
46
1STEP
* STEP BY STEP (1-STEP) RUN
If this value is set in "1", the "step by step run" function is available.
By executing the user program step by step, the operation of the
program can be checked in detail. It is stopped at every 1-step and
continuously run by run input.
0