61
[2] Diagnosing Problems Using Error Codes
If a problem occurs, please check the following before calling for service.
(1) Check the error code against the table below.
(2) Check for possible causes of problems listed in the "Cause" column that correspond to the error code.
(3) If the error codes that appear on the display are not listed in the table below, or no problems were found with the
items listed in the "Cause" column, please consult your dealer or servicer.
Diagnosing Problems Using Error Codes
Error
code *1
(PCB *2
RC
M-NET)
Error type
Cause
(Installation/Setting error)
Cause
(Parts problems)
Error reset *3
Unit
side
(PCB)
Remote
SWS1 Operation
SW
0100
Unreset errors
Some of the errors have not been reset.
4106
(
254
)
Power failure
Power failure occurred when the
operation switch is switched on.
4106
(
255
)
Power supply fault
• Transmission power board fault
2613
Water flow drop
• Water flow control valve fault
• Pump fault
1301
Vacuum protection fault
• Outside temperature is below the
minimum usage temperature.
• Sudden frosting or heavy snow has
clogged the heat exchanger.
• Low-pressure sensor fault
• Suction refrigerant temperature
thermistor fault
• Electric expansion valve fault on the main
circuit
• Fan motor error/broken motor wire
• Refrigerant shortage (gas leakage)
1302
High pressure fault
• Electronic expansion valve fault
• High-pressure sensor fault
• Water flow control valve fault
• Pump fault
1104
Low evaporation temperature fault
• Low-pressure sensor fault
• Suction refrigerant temperature
thermistor fault
• Electric expansion valve fault on the main
circuit
• Fan motor error/broken motor wire
• Refrigerant shortage (gas leakage)
2601
Water supply cutoff (Water flow rate sensor)
Water flow drop
• Water flow control valve fault
• Pump fault
• Water flow rate sensor
2601
(
2
)
Secondary side water supply cutoff error
Water circuit air entrainment, water
strainer clogged
Flow sensor fault, pump fault, motor-
operated valve fault, water flow rate control
valve fault
2138
Outlet water temperature fault (low temp)
• Fan motor error/broken motor wire
• Refrigerant shortage (gas leakage)
WT08219X05.book 61 ページ 2018年10月1日 月曜日 午後7時47分
Содержание QAHV
Страница 83: ......