49
(6) Setting the total number of units for a multiple system
Setting the unit addresses
Refer to “(4) System configuration procedures : Multiple system” (page 29).
Step 0
Set the ON/OFF
switch (SWS1) to
OFF.
Set SWS1 to OFF from the remote controller or with the local switch.
Settings cannot be changed unless the ON/OFF switch is set to OFF.
Step 1
Set the dip switches
SW2 and SW3.
Set the dip switches on the circuit board as follows to select how external inputs are received.
Step 2
Select the desired
item with the push
switch SWP3.
The item codes shown in the table below will appear in order every time the push switch
SWP3 is pressed.
Use the push switches SWP1 and SWP2 to change the value of the selected item.
The value will keep blinking while it is being changed.
Step 3
Press the push
switches SWP1 (
↑
)
or SWP2 (
↓
) to
increase or
decrease the value.
Step 4
Press the push
switch SWP3 to
save the change.
Press SWP3 once within one minute of changing the setting with SWP1 or SWP2 to save the
setting.
Once the new setting is saved, the display will stop blinking and stay lit. The display will, then,
return to the item code display mode.
If SWP3 is not pressed within one minute, the change will not be saved and the display will
return to the item code display mode.
Step 5
Turn the power back
on.
Reset the system.
After changing the settings, re-initialize the system according to the procedures detailed on
page 32.
SW2
SW3
-10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
ON
ON
ON
Setting table
*1 Enter the total number of units including the main unit. Applicable only to the main unit.
*2 0: Sub unit
1: Main sensor
2: Sub sensor (For six-sensor method)
*3 Set the address of the sub sensor for six-sensor method.
*4 0: Secondary side control disabled
1: Secondary side control enabled
Item code
Increments
Lower limit
Upper limit
Initial value
Unit address
105
1
1
8
2
Total number of units in the system*1
106
1
0
16
1
AE-200 connection
107
2
0
2
0
Own unit role*2
110
1
0
2
0
Main sensor address
111
1
1
50
1
Sub sensor address*3
112
1
1
51
51
Secondary circuit control*4
121
1
0
1
0
Note
The new setting will not be saved unless a reset is performed.