4. Perform an initial setup on the unit
(1) Set the sub unit rotary switch SWU3 on the unit (labeled A in the figure
at right) to "F."
[EEEE] will appear in LED1 (labeled B in the figure at right). *1
(2) Press and hold the sub unit push switch (SWP3) (labeled C in the figure
at right) for one second or longer.
• While the system is starting up [9999] will appear on LED1 (labeled B in
the figure at right).
(3) Set the main unit rotary switch SWU3 on the unit (labeled A in the figure
at right) to "F."
[EEEE] will appear in LED1 (labeled B in the figure at right). *1
(4) Press and hold the main unit push switch (SWP3) (labeled C in the
figure at right) for one second or longer.
• While the system is starting up [9999] will appear on LED1 (labeled B in the figure at right).
(5) When start-up is complete, a control property [0001] will appear.
• Then, five seconds later, [FFFF] will appear. *2
(6) Set the rotary switch SWU3 (labeled A in the figure at right) back to "0."
The start-up process is complete, and the settings for such items as clock, peak-demand control, schedule, and
thermistor settings can now be made.
*1 If the start-up process has already been completed, [FFFF] (instead of [EEEE]) will appear when the rotary switch
SWU3 is set to "F."
*2 [--ng] is displayed before the water flow rate adjustment operation is performed.
Refer to “2. Switch on the power to the unit.” on page 27 for how to cancel [--ng].
Slide switch (SWS1) settings
Individual system
Multiple system (SWS1 in the SUB circuit on both the main and sub units will be ineffective.)
* When connecting AE-200 and remote controller (PAR-W31MAA) simultaneously, make the settings above, and
then turn off the power, turn it back on, and set “1” for item code [105] for the unit to which a remote controller
is connected. After these settings, perform the procedures described in (5) on page 32.
SWS1 Setting
Unit Operation
LOCAL
Follows the input signal of the MAIN circuit
OFF
Ignores the signal input
REMOTE
Follows the input signal fed through a dry contact interface
SWS1 Setting
Unit Operation
Main unit
MAIN circuit
Sub unit
MAIN circuit
Main unit
Sub unit
LOCAL
LOCAL
Follows the input signal of the Main unit
Follows the input signal of the Sub unit
OFF
Ignores the signal input
REMOTE
Follows the input signal of the Sub unit
OFF
LOCAL
Ignores the signal input
Ignores the signal input
OFF
REMOTE
REMOTE
LOCAL
Follows the input signal fed through a dry
contact interface
Follows the input signal of the Main unit
OFF
Ignores the signal input
REMOTE
Follows the input signal of the Main unit
A
B
C
ON
1
23
456
7
89
1
0
ON
1
23
456
7
89
1
0
ON
1
23
456
7
89
1
0
Main unit
10’s digit (0) 1’s digit (1)
(0)
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
WT08219X05.book 31 ページ 2018年10月1日 月曜日 午後7時47分