5
CAUTION
WARNING
CAUTION
To reduce the risk of current leakage, overheating, smoke, or
fire, use properly rated cables with adequate current carrying
capacity.
Keep the unsheathed part of cables inside the terminal
block.
If unsheathed part of the cables come in contact with each
other, electric shock, smoke, or fire may result.
Proper grounding must be provided by a licensed
electrician. Do not connect the grounding wire to a gas
pipe, water pipe, lightning rod, or telephone wire.
Improper grounding may result in electric shock, smoke, fire,
or malfunction due to electrical noise interference.
To reduce the risk of current leakage, wire breakage, smoke,
or fire, keep the wiring out of contact with the refrigerant
pipes and other parts, especially sharp edges.
To reduce the risk of electric shock, shorting, or malfunctions,
keep wire pieces and sheath shavings out of the terminal
block.
Transportation and repairs
The unit should be moved, disassembled, or repaired
only by qualified personnel. Do not alter or modify the
unit.
Improper repair or unauthorized modifications may result in
refrigerant leakage, water leakage, injury, electric shock, or
fire.
After disassembling the unit or making repairs, replace
all components as they were.
Failing to replace all components may result in injury, electric
shock, or fire.
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
To reduce the risk of shorting, electric shock, fire, or
malfunction, do not touch the circuit board with tools or with
your hands, and do not allow dust to accumulate on the
circuit board.
IMPORTANT
To avoid damage to the unit, use appropriate tools to install,
inspect, or repair the unit.
To reduce the risk or malfunction, turn on the power at least
12 hours before starting operation, and leave the power
turned on throughout the operating season.
Recover all refrigerant from the unit.
It is punishable by law to release refrigerant into the
atmosphere.
Do not unnecessarily change the switch settings or
touch other parts in the refrigerant circuit.
Doing so may change the operation mode or damage the
unit.
To reduce the risk of malfunctions, use the unit within its
operating range.
Do not switch on or off the main power in a cycle of
shorter than 10 minutes.
Short-cycling the compressor may damage the compressor.
To maintain optimum performance and reduce the risk of
malfunction, keep the air pathway clear.
To ensure proper operation of the unit, periodically
check for proper concentration of anti-freeze.
Inadequate concentration of anti-freeze may compromise the
performance of the unit or cause the unit to abnormally stop.
Take appropriate measures against electrical noise
interference when installing the air conditioners in
hospitals or facilities with radio communication
capabilities.
Inverter, high-frequency medical, or wireless communication
equipment as well as power generators may cause the air
conditioning system to malfunction. Air conditioning system
may also adversely affect the operation of these types of
equipment by creating electrical noise.
Check the water system, using a relevant manual as a
reference.
Using the system that does not meet the standards (including
water quality and water flow rate) may cause the water pipes
to corrode.
To reduce the risk of power capacity shortage, always use a
dedicated power supply circuit.
This appliance is intended to be used by expert or trained
users in shops, in light industry and on farms, or for
commercial use by lay persons.
WT08219X05.book 5 ページ 2018年10月1日 月曜日 午後7時47分
Содержание QAHV
Страница 83: ......