50
(7) Selecting the item that normally appears on the LED
(*1)
(*2)
SW2
SW3
Display content
-10
5
6
7
8
9
10
OFF
OFF
OFF
ON
OFF
OFF
OFF
Displays the operation mode.(*1)
OFF
OFF
ON
ON
OFF
OFF
OFF
Displays the operation mode.(*2)
OFF
ON
ON
OFF
OFF
OFF
OFF
Displays the current water temperature.
OFF
ON
OFF
OFF
OFF
OFF
OFF
Displays the water-temperature setting.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Displays the high and low refrigerant pressures.
The dot lights up when the operation signal is on.
The dot lights off when the operation signal is off.
"A" will be displayed while the compressor is in operation.
"S" will be displayed while the compressor is stopped.
"S" will be displayed while the fan is forced to operate.
"-" will be displayed when this function is disabled.
"d" will be displayed when the peak-demand control function is enabled.
"-" will be displayed when this function is disabled.
Displays the operation mode.
"H" will be displayed during water-heating operation.
"d" will be displayed during a defrost cycle.
"F" will be displayed while the pump is being operated to prevent freeze-up.
Displays the system control mode.
"S" will be displayed when the multiple system control option is used.
"A" will be displayed when the individual system control option is used.