23
[2] Switch Types and the Factory Settings
(1) Switch names and functions
There are four main ways to set the settings as follows:
1
Dip switches (SW1 - SW3)
2
Dip switches used in combination with the push switches
3
Rotary switches
4
Slide switches
See below for how these switches are used to set certain items.
Different types of switches on the PCB
Set the slide switch SWS2 on the board inside the control box to the
lower side
during the trial run.
By default, it is set to the upper side for forced stop of the pump and compressor to prevent the pump
being damaged by the anti-freezing process in no water passing status or valve closed status before
the test run.
Upper side: A (under preparation)
Lower side: B (auto)
Always set to the lower side.
* Setting to the upper side forcefully stops the pump and compressor thus the unit does not
operate.
* When SWS2 is set to the upper side, the display shows “P.OFF” and the setting cannot be
made. When “P.OFF” appears, set SWS2 to the lower side.
Discharge air outlet
Service panel
Control box
Intake air inlet
Rotary switch (SWU3) (0-F)
Rotary switch (SWU2) (0-9)
Rotary switch (SWU1) (0-9)
Slide switch (SWS1)
(LOCAL, OFF, and REMOTE
from the top)
Push switch (SWP1) "UP"
Push switch (SWP2) "DOWN"
Push switch (SWP3) "ENTER"
Slide switch (SWS2) *
(A and B from the top)
Switches
[Entire view of a PCB]
[Enlarged view of the switches]
LED display
Dip switch (SW1)
Dip switch (SW2)
Dip switch (SW3)
Slide the dip
switches; do not
push down the
switches.
Water outlet
Water inlet
WT08219X05.book 23 ページ 2018年10月1日 月曜日 午後7時47分