55
Note:
• Make sure the cables are not coming out of the rubber bushing cut.
• When threading the wiring through the rubber bushing, make sure the rubber bushing will not come off the sheet
metal on the control box guard.
• When tying the supplied tie band around the rubber bushing, make sure to leave no gap between the ends.
A power wire exceeding the specified power wire thickness cannot be connected to the power terminal block (TB2).
Use a separate pull box.
To ensure that the transmission cable is not affected by electrical noise from the power cable, route the power cable
away from the transmission cable (distance of at least 50 mm (2 in)).
Top view
Wiring
Wiring
Rubber bushing
Rubber bushing
(oval part)
Rubber bushing
(oval part)
Cut
Wiring
Cables are coming out of the rubber bushing.
Top view
Cross-sectional view
Sheet metal on
the guard
Rubber bushing
Sheet metal on
the guard
Rubber bushing
Tie band
Overlapped
rubber bushing
Cut on the
rubber bushing
Cut on the
rubber
bushing
Approx. 20 mm (13/16 in)
There is a gap in
the rubber
bushing.
<<Important>>
When putting the tie band on the rubber bushing, make sure the
ends of the rubber bushing overlap each other as shown in the
figure at left.
* If there is a gap, water from snow or rain may enter, resulting in
equipment damage.