4
CAUTION
WARNING
CAUTION
The unit should be installed only by personnel certified
by Mitsubishi Electric according to the instructions
detailed in the Installation/Operation Manual.
Improper installation may result in refrigerant leakage, water
leakage, injury, electric shock, or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged base, it may fall and cause
injury.
Remove packing materials from the unit before operating
the unit. Note that some accessories may be taped to the
unit. Properly install all accessories that are required.
Failing to remove the packing materials or failing to install
required accessories may result in refrigerant leakage,
oxygen starvation, smoke, or fire.
Consult your dealer and take appropriate measures to
safeguard against refrigerant leakage and resultant oxygen
starvation. An installation of a refrigerant gas detector is
recommended.
Any additional parts must be installed by qualified personnel.
Only use the parts specified by Mitsubishi Electric.
Take appropriate safety measures against wind gusts and
earthquakes to prevent the unit from toppling over and
causing injury.
Be sure to install the unit horizontally, using a level.
If the unit is installed at an angle, it may fall and cause injury
or cause water leakage.
The unit should be installed on a surface that is strong
enough to support its weight.
As an anti-freeze, use ethylene glycol or propylene
glycol diluted to the specified concentration.
The use of other types of anti-freeze solution may cause
corrosion and resultant water leakage. The use of flammable
anti-freeze may cause fire or explosion.
Do not install the unit on or over things that are
vulnerable to water damage.
When the indoor humidity exceeds 80% or if the drain water
outlet becomes clogged, condensation may drip from the
indoor unit onto the ceiling or floor.
All drainage work should be performed by the dealer or
qualified personnel according to the instructions
detailed in the Installation Manual.
Improper drainage work may cause rain water or drain water
to enter the buildings and damage the furnishings.
Pipe installation
To prevent explosion, do not heat the unit with refrigerant gas
in the refrigerant circuit.
Check for refrigerant leakage at the completion of
installation.
If leaked refrigerant comes in contact with a heat source,
toxic gas may be generated.
Check that no substance other than the specified
refrigerant (R744) is present in the refrigerant circuit.
Infiltration of other substances may cause the pressure to
rise abnormally high and cause the pipes to explode.
To keep the ceiling and floor from getting wet due to
condensation, properly insulate the pipes.
Piping work should be performed by the dealer or
qualified personnel according to the instructions
detailed in the Installation Manual.
Improper piping work may cause water leakage and damage
the furnishings.
Electrical wiring
To reduce the risk of wire breakage, overheating, smoke, and
fire, keep undue force from being applied to the wires.
Properly secure the cables in place and provide
adequate slack in the cables so as not to stress the
terminals.
Improperly connected cables may break, overheat, and
cause smoke or fire.
To reduce the risk of injury or electric shock, switch off the
main power before performing electrical work.
All electric work must be performed by a qualified
electrician according to the local regulations, standards,
and the instructions detailed in the Installation Manual.
Capacity shortage to the power supply circuit or improper
installation may result in malfunction, electric shock, smoke,
or fire.
To reduce the risk of electric shock, smoke, or fire, install an
inverter circuit breaker on the power supply to each unit.
Use properly rated breakers and fuses (inverter breaker,
Local Switch < Type-B fuse>, or no-fuse
breaker).
The use of improperly rated breakers may result in
malfunctions or fire.
WT08219X05.book 4 ページ 2018年10月1日 月曜日 午後7時47分
Содержание QAHV
Страница 83: ......