65
*1: The codes in the parentheses in the "Error code" column indicate error detail codes.
*2: If an error occurs, error codes shown above will appear in the 4-digit digital display on the PCB.
*3: Definition of symbols in the "Error reset" column.
: Errors that can be reset regardless of the switch settings
: Errors that can be reset if the remote reset setting on the unit is set to "Enable" (factory setting)
Errors that cannot be reset if the remote reset setting on the unit is set to "Disable"
: Errors that cannot be reset
: Errors that will be automatically cancelled once its cause is removed
*4: Power failure will be detected as an error only when the "Automatic recovery after power failure" setting on the unit is set to "Disable."
(The default setting for the "Automatic recovery after power failure" setting is "Enable.")
*5: Depending on the system configuration, if communication error lasts for 10 minutes or longer, units will make an abnormal stop.
This error can be reset by turning off and then back on the unit's power.
*6: This error code will appear when multiple errors occur that are reset in different ways and when one or more of these errors have not been reset. This error can be
reset by turning off and then back on the unit's power.
*7: Before resetting this error, remove its causes. Resuming operation without removing the causes of heat exchanger freeze up will cause heat exchanger damage.
6830
Remote
controller
error (incl.
remote
controller
wiring
fault)
Address overlap
There are two or more of the same
address.
7109
Non-consecutive address, system error
Address setting error
(Non-consecutive address)
6831
Remote controller signal reception error 1 Remote controller cable is not
connected.
Broken wiring
• Broken remote controller wiring
• Main control board communication circuit
fault
6832
Remote controller signal transmission
error
Communication error due to external
noise interference
• Main control board communication circuit
fault
6833
Remote controller over current
Remote controller cable is short
6834
Remote controller signal reception error 2 Communication error due to external
noise interference
• Main control board communication circuit
fault
7130
Multiple
system
error
Incompatible combination of units
Different types of units are connected to
the same system.
7102
No.-of-connected-unit setting is incorrect. No.-of-connected-unit setting is
incorrect (Main unit).
4126
(
1
)
Analog input error
(Control board (MAIN) CN421)
Analog input type fault
Set Item code 1075
• Broken or Open 4-20mA signal output
device wiring (CN421)
6500
Communication error between the main and sub units
Communication error between the MAIN and SUB
circuits
6600
Transmission line power supply PCB fault
Communication error between the main and sub units
(Simple multiple unit control mode)
*7
Communication error due to external
noise interference
• Broken wiring to the transmission power
supply circuit board (between the main
and sub units)
• Transmission power supply PCB
communication circuit fault
6602
6603
6606
6607
6608
5701
Water flow adjusting value limit switch error
Water flow rate control valve fault
2518
Secondary side hot water temperature reduction error Insufficient pump capacity
Outdoor air temperature is below
operating range lower limit
Secondary side pump fault
Secondary side heat exchanger
deteriorated
Flow sensor fault
2616
(
1
)
Secondary side heat exchanger error
(Deterioration of heat exchanger)
Heat exchanger deteriorated
2616
(
2
)
Secondary side heat exchanger error
(Heat exchanger selection error)
Initial heat exchanger selection error
Error
code *1
(PCB *2
RC
M-NET)
Error type
Cause
(Installation/Setting error)
Cause
(Parts problems)
Error reset *3
Unit
side
(PCB)
Remote
SWS1 Operation
SW