36
3
Press SWP1 or SWP2 to display the operation result (flow rate characteristic) corresponding each flow rate code
‘dxx’ in Table 1 and write them down.
Table 1
<Check result>
4
Check the following.
↓
Check the checkbox.
□
All places with flow rate valve opening 1000 through 100 are 2 L or above?
If 2 L/min or below, air may not be bled out. Perform an air bleeding operation and water flow rate
adjustment operation again.
□
When there are multiple units, the values of the same pump output opening and the same valve opening
are not greater or less than those for other units by 10% and 2 L/min or more.
(In multiple-unit system, perform a water flow rate adjustment operation at the same time.)
□
All the values (item codes d01 through d09) are not “0” when the pump output opening is 16%. (Not
whole air is bled out.)
(Note 1) Change SW2-9 and SW2-3 as a stopgap procedure as shown in the table below, and then turn the power
on.
(Note 2) The table below shows the water flow rate adjustment operation status in 4 figures when the PCB DIP
switch is set as shown in Note 3.
(Note 3) PCB DIP switch settings
Close <------------------ Water flow rate adjust valve opening ------------------> Open
Pump output opening/water flow rate
adjust valve opening
1600
1400
1200
1000
800
600
400
200
100
Flow rate (pump output opening 16%)
d01
d02
d03
d04
d05
d06
d07
d08
d09
Flow rate (pump output opening 27%)
d10
d11
d12
d13
d14
d15
d16
d17
d18
Flow rate (pump output opening 100%)
d19
d20
d21
d22
d23
d24
d25
d26
d27
Close <------------------ Water flow rate adjust valve opening ------------------> Open
Pump output opening/water flow rate
adjust valve opening
1600
1400
1200
1000
800
600
400
200
100
Flow rate (pump output opening 16%)
Flow rate (pump output opening 27%)
Flow rate (pump output opening 100%)
Multiple unit change-over switch
SW2-9
Local/internal change-over switch
SW2-3
When startup operation has not completed
OFF
ON
When startup operation has completed
-
-
Water flow rate adjustment operation status
Display
Not completed
- - n g
Completed
- - - g
In operation
- i n g
SW2
SW3
-10
-5
-6
-7
-8
-9
-10
ON
OFF
OFF
OFF
ON
ON
OFF
WT08219X05.book 36 ページ 2018年10月1日 月曜日 午後7時47分