64
4220
4225
(
108
)
Inverter
error
Voltage
related
problems
during
operation
Bus voltage drop protection
Momentary power failure/power failure
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
Voltage drop
• INV board CNDC2 wiring fault
• INV board fault (4220)
• Fan board fault (4225)
• 72C fault
• Diode stack failure
4220
4225
(
109
)
Bus voltage rise protection
Incorrect power supply voltage
• INV board fault (4220)
• Fan board fault (4225)
4220
4225
(
111
)
Logic error
Malfunction due to external noise
interference
• Faulty grounding
• Improper transmission and external
wiring installation
(Shielded cable is not used.)
• Low-voltage signal wire and high-
voltage wire are in contact.
(Placing the signal wire and power
wire in the same conduit)
• INV board fault (4220)
• Fan board fault (4225)
4220
4225
(
131
)
Voltage meter error at start up
(Bus voltage drop protection at start up
(detected by the Main unit side))
Power supply voltage drop
• INV board fault (4220)
• Fan board fault (4225)
4230
4235
Heatsink fault
(Heatsink overheat protection)
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
Clogged heatsink cooling air passage
• Fan motor fault
• INV board fan output fault
• THHS sensor fault
• IPM error (loose terminal screws,
cracked due to swelling)
4240
4245
Overload protection
Short-cycling of air (reduced air flow)
Clogged heatsink cooling air passage
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
• THHS sensor fault
• Current sensor fault
• INV board fan output fault
• INV circuit fault
• Compressor fault
5301
5305
(
115
)
ACCT sensor fault
• INV board fault
• Ground fault of the compressor and IPM
error
5301
5305
(
116
)
DCCT sensor
• Poor contact at the INV board connector
CNCT
• Poor contact at the INV board connector
DCCT
• Ground fault of the compressor and IPM
error
5301
5305
(
117
)
ACCT sensor/circuit fault
• Poor contact at the INV board connector
CNCT2 (ACCT)
• ACCT sensor fault
5301
5305
(
118
)
DCCT sensor/circuit fault
• Poor contact at the INV board connector
CNCT
• Poor contact at the INV board connector
DCCT
• DCCT sensor fault
• INV board fault
5301
5305
(
119
)
Open-circuited IPM/loose ACCT sensor
• Disconnected ACCT sensor (CNCT2)
• ACCT sensor fault
• Broken compressor wiring
• INV circuit fault (IPM error etc.)
5301
5305
(
120
)
Faulty wiring
• ACCT sensor is connected in the wrong
phase.
• ACCT sensor is connected in the wrong
orientation.
5110
(
01
) (
05
)
THHS sensor/circuit fault
• THHS sensor contact failure
• THHS sensor fault
• INV board fault
0403
(
01
) (
05
)
Serial communication error
• Communication error between control
board and INV board (noise interference,
broken wiring)
IPM system error
INV board switch setting error
• Wiring or connector connection between
connectors on IPM-driven power supply
circuit
• INV board fault
Error
code *1
(PCB *2
RC
M-NET)
Error type
Cause
(Installation/Setting error)
Cause
(Parts problems)
Error reset *3
Unit
side
(PCB)
Remote
SWS1 Operation
SW
WT08219X05.book 64 ページ 2018年10月1日 月曜日 午後7時47分
Содержание QAHV